Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão

HART Output Isolator FB4302B2

FB4302B2
  • 1-channel
  • Outputs with plug-in Ex e terminals
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Analog output module for 0/4 mA ... 20 mA
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Output with watchdog
  • Permanently self-monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Folhas de dados: Dados técnicos do  FB4302B2

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation0.8 W
Power consumption0.95 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog output
Number of channels1
Suitable field devices
Field deviceProportional Valve
Field device [2]I/P converters
Field device [3]on-site display
Connectionchannel I: 2/3+, 4/5-
Current0 ... 25 mA short-circuit protected
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitNo
Open-circuitdeviation of preset output value > 0.5 mA
Load750 Ω max.
HART communicationyes
HART secondary variableMODBUS: yes; all other bus systems: no
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Transfer characteristics
Deviation
After calibration0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature0.1 %/10 K of the signal range
Refresh time100 ms
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1) red: line fault (lead breakage or short circuit)
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
ConnectionEx e spring terminal with protective cover
Massapprox. 350 g
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-type examination certificateBVS 11 ATEX E 093 X
MarkingEx-Hexagon II 2 G Ex db eb IIC T4
Galvanic isolation
Output/power supply, internal bussafe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020
EN 60079-1:2014
EN 60079-7:2015+A1:2018
International approvals
ATEX approvalBVS 11 ATEX E 093X
General information
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: FB4302B2

Datasheet: FB4302B2

DatasheetTipo de ArquivoTamanho do Arquivo
Datasheet FB4302B2PDF501 KB
Datenblatt FB4302B2PDF503 KB

Documents: FB4302B2

ManualsTipo de ArquivoTamanho do Arquivo
FB Hardware ManualPDF9157 KB
FB-Hardware-HandbuchPDF9182 KB
Instruction manuals
ИнструкцииPDF144 KB
Návod k poużitíPDF136 KB
Instruktions manualPDF135 KB
Instruction manualPDF61 KB
KasutusjuhendPDF133 KB
KäyttöohjePDF131 KB
Manuel d'instructionsPDF78 KB
BetriebsanleitungPDF63 KB
Οδηγίες χρήσηςPDF148 KB
HandleidingPDF138 KB
Instruction manual / BetriebsanleitungPDF136 KB
Használati útmutatóPDF137 KB
Manuale di istruzioniPDF76 KB
Lietošanas pamācībaPDF136 KB
Instrukciju vadovasPDF138 KB
Instrukcja obsługiPDF139 KB
Manual de instruçõesPDF138 KB
Manual de utilizarePDF137 KB
Návod na poużitiePDF137 KB
Navodila za uporaboPDF134 KB
Manual de instruccionesPDF78 KB
ManualPDF133 KB
Application reports
Application Report - Communication Redundancy for Uninterrupted OperationPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesPDF208 KB
Application Report - Space Saving Extension for Existing PlantsPDF300 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsPDF371 KB
Applikationsbericht - Platzsparende Erweiterung für bestehende AnlagenPDF300 KB
Applikationsbericht - Redundanz der Kommunikation für ungestörten BetriebPDF530 KB
Applikationsbericht - Remote-I/O-Systeme Typ LB und FB für digitale Anbindung analoger FeldgerätePDF208 KB
Applikationsbericht - Remote-I/O-Systeme für effiziente AnlagendigitalisierungPDF365 KB
Documents
Functional Safety ManualPDF2422 KB
Handbuch funktionale SicherheitPDF2435 KB

CAD+CAE: FB4302B2

EPLANTipo de ArquivoTamanho do Arquivo
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ104 KB

Approvals+Certificates: FB4302B2

CertificatesTipo de ArquivoTamanho do Arquivo
Europe DEKRA EXAMPDF618 KB
Lloyd's Register MarinePDF557 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF1041 KB